www.DaikinApplied.com 89 IM 1287-6 • REBEL APPLIED ROOFTOP
Table 14: Minimum Room Area Multipliers by Altitude
Altitude (Meters) Minimum Room Area Multiplier
0 1
305 1.047
500 1.078
750 1.117
1000 1.156
1250 1.195
1500 1.234
1750 1.273
2000 1.312
2250 1.351
2500 1.39
2750 1.429
3000 1.468
3250 1.507
3500 1.546
Figure 161: Required Minimum Room Area Chart