37
2
Split Sky Air • Outdoor Units
9
Outdoor Units • R-410A • REQ-B7
2 Specifications
2 - 4 Safety device settings
REQ71125B7
Model
Safety device
REQ71B7V3B REQ100B7V3B REQ125B7W1B
REQ71B7W1B REQ100B7W1B
Fan motor thermal protector
Off 135 ±5°C
On 95 ±15°C
HPS
Off 4,15 Mpa
On 3.2 Mpa
LPS
Off -0.03 Mpa
On 0.05 Mpa
Max discharge temperature By thermistor and software control
Overcurrent relay By overcurrent sensor and software control
4TW26321-2B
+0
-0,10
+0,15
-0,15
+0,02
-0,02
+0,03
-0,03