unIT oPTIons
www.DaikinApplied.com 89 IM 893-10 • ROOFPAK SINGLEZONE UNITS
Table 19: Propeller Exhaust Fan Troubleshooting
Problem Cause Corrective Action
Reduced Airow
System resistance is too high.
Check backdraft dampers for proper operation
Remove obstructions in ductwork
Clean dirty lters
Check for adequate supply for air exhaust fans or
exhaust air for supply fans
Unit running backwards. See Prestarting Checks on page 87
Fan speed too low. Increase fan speed
Excessive dirt on propeller. Clean propeller
Excessive Noise
Bearings
Tighten bearing collars and setscrews
Lubricate bearings
Replace defective bearings
V-Belt drive
Tighten pulleys on motor shaft and fan shaft
Adjust belt tension
Align pulleys
Replace worn belts or pulleys
Excessive vibration
Clean dirt build-up from propeller
Check all setscrews and fasteners for tightness
Check for worn bearing
Correct propeller imbalance
Check for loose dampers, guards or ductwork
Defective motor Replace motor.
Figure 95: Propeller Exhaust Fan Replacement Parts List
9
8
7
1 0
6
5
4
1
2
3
1. F an pa n e l
2. P rop e l l er
3. D rive fr ame
ch a n n e l ( 2)
4. M oto r pl ate
5. M oto r
6. M oto r pu lley
7. S h a ft pu l l ey
8. F an sh aft
9. B e a rin g s
10. B elt
11. B a e ring
pl at
e
11