8 | Charging refrigerant
Installer reference guide
47
RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
8.3 Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the following chapters:
"2General safety precautions"[45]
"7.1Preparing refrigerant piping"[435]
8.4 To determine the additional refrigerant amount
For ARXM71R
If the total liquid piping
length is…
Then…
≤10m Do NOT add additional refrigerant.
>10m R=(total length (m) of liquid piping⁠–⁠10m)×0.035
R=Additional charge (kg) (rounded in units of
0.01kg)
For other outdoor units
If the total liquid piping
length is…
Then…
≤10m Do NOT add additional refrigerant.
>10m R=(total length (m) of liquid piping⁠–⁠10m)×0.020
R=Additional charge (kg) (rounded in units of
0.01kg)
INFORMATION
Piping length is the one-way length of liquid piping.
8.5 To determine the complete recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
8.6 To charge additional refrigerant
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.

Table of Contents

Other manuals for Daikin RXF60D5V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXF60D5V1B and is the answer not in the manual?

Daikin RXF60D5V1B Specifications

General IconGeneral
BrandDaikin
ModelRXF60D5V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals