14 | Maintenance and service
Installer reference guide
62
RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
▪ Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked
heat exchanger can lead to too low pressure or too high pressure leading to
worse performance.
14.4 About the compressor
When servicing the compressor keep in mind following precautions:
DANGER: RISK OF ELECTROCUTION
▪ Use this compressor on a grounded system only.
▪ Turn the power off before servicing the compressor.
▪ Reattach the switch box cover and service lid after servicing.
CAUTION
Always wear safety goggles and protective gloves.
DANGER: RISK OF EXPLOSION
▪ Use a pipe cutter to remove the compressor.
▪ Do NOT use the brazing torch.
▪ Use approved refrigerants and lubricants only.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the compressor with bare hands.