Preparation
Installer reference guide
12
RZAG71~140N7V1+Y1
Sky Air Alpha-series
4P573381-1 – 2019.04
Requirement Limit
71 100 125+140
5 Maximum difference between branch
lengths
Pair: N/A —
Twin: L2–L3≤Limit 10m
Triple: L2–L4≤Limit — 10m
Double twin:
▪ L2–L3≤Limit
▪ L4–L5≤Limit
▪ L6–L7≤Limit
▪ (L2+L4)–(L3+L7)≤Limit
— 10m
6 Maximum height between indoor and
outdoor
Pair, twin, triple and double twin: H1≤Limit 30m
7 Maximum height between indoors Pair: N/A
Twin, triple and double twin: H2≤Limit
0.5m
(a) Parenthesised figure represents the equivalent length.
Example
If the system layout is as follows… Then the requirements are…
▪ RZAG125
▪ Triple:
▪ Østandard
1 3m≤L1+L4
2 L1+L2≤85m (100m)
3 L1+L2+L3+L4≤85m
4 L2≤20m
5 L2–L4≤10m
6 H1≤30m
7 H2≤0.5m
5.3.2 Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Ambient
temperature
Humidity Minimum thickness
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
5.4 Preparing electrical wiring
5.4.1 About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
INFORMATION
Also read "6.7.5 Specifications of standard wiring
components"on page24.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.