Installation
Installer reference guide
24
RZAG71~140N7V1+Y1
Sky Air Alpha-series
4P573381-1 – 2019.04
6.7.5 Specifications of standard wiring components
Component V1 Y1
71 100 125~140 71 100 125 140
Power supply cable MCA
(a)
18.8A 23.3A 28.8A 12.3A 15.4A 15.7A 15.4A
Voltage range 220~240V 380~415V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with applicable legislation
Interconnection cables Minimum cable section of 2.5 mm² and applicable for 230 V
Recommended field fuse 20A 32A 16A
Earth leakage circuit breaker Must comply with applicable legislation
(a) MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).
6.7.6 To connect the electrical wiring on the
outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "6.2.2 To open the outdoor
unit"on page13.
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cables and power supply as
follows:
c
a
d
e
1~ 50 Hz
220-240 V
3N~ 50 Hz
380-415 V
V1 Y1
L1 L2 L3
L1 L2 L3
N
b
b
a
a
a
I, II, III, IV Pair, twin, triple, double twin
M, S Master, slave
a Interconnection cables
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e User interface
INFORMATION
Some indoor units may need a separate power supply in
order to guarantee maximum capacity. See the installation
manual of the indoor unit.
V1
a
b
d
c
Y1
a
b
d
c
a Interconnection cable
b Power supply cable
c Earth
d Cable tie
4 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration above.
5 Choose a knockout hole and remove the knockout hole by
tapping on the attachment points with a flat head screwdriver
and a hammer.
6 Route the wiring through the frame and connect the wiring to
the frame at the knockout hole.