Loading...
SiBE121021_C Service Check Function
Service Diagnosis 303
3.2.4 BRC7E530W/531W, BRC7F532F/533F, BRC7EA63W/66
To find the error code, proceed as follows:
Step Action
1 Press the [Inspection / Test] button to enter the inspection mode. Then the figure ā€œ0ā€
blinks on the UNIT No. display.
2 Press the UP or DOWN button and change the UNIT No. until the receiver of the remote
controller starts to beep.
[Inspection / Test] button
(R14392)
UP button
DOWN button
(R14424)
If you hear... Then...
3 short beeps Follow all steps below.
1 short beep Follow steps 3 and 4. Continue the
operation in step 4 until you hear a
continuous beep. This continuous
beep indicates that the error code
is confirmed.
1 continuous beep There is no abnormality.