Troubleshooting for Outdoor Unit SiBE121021_C
342 Service Diagnosis
Troubleshooting
Check No.01
Refer to P.362
Check No.12
Refer to P.364
Check No.17
Refer to P.368
Check No.18
Refer to P.368
Check No.19
Refer to P.369
(R14558)
Caution
Replace the fan motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 17
Check the
installation condition.
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi NX FFQ35B8V1B and is the answer not in the manual?

Daikin Super Multi NX FFQ35B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi NX FFQ35B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals