InsTallaTIon
www.DaikinApplied.com 7 IM 1137-4 • TEMPLIFIER
®
MODEL TGZ
Once the unit has been located, set the unit in place and level
with a spirit level. When spring-type isolators are required,
install springs running under the main unit supports.
The unit should be set initially on shims or blocks at the listed
spring free height. When all piping, wiring, ushing, charging,
etc., is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed. Refer to Table 12
on page 24 for correct lifting and mounting locations.
Installation of spring isolators requires exible piping
connections and at least three feet of exible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
A rubber anti-skid pad should be used under isolators if hold-
down bolts are not used.
Table 1: Vibration Mounting Location and Kit Number