32
Maintenance
The unit must be checked on a routine basis to ensure performance. Routine check is the best way to reduce
downtime and waste. The following needs to be checked on a routine basis:
Items Monthly Quarterly
Once half a
year
Once a year If necessary
1. Compressor
Performance appraisal; whether there is
abnormal sound
Whether wires are securely connected
Whether the working current is abnormal
(uctuation: 10%)
Discharge air temperature of the compressor
Check the oil level
Check the color of the lubricant
2. Controller
Check parameter settings
Check protective device
Delay protector
Phase order protector
High/low pressure switch
Differential water pressure switch/water ow
switch
Overload protector
Protector against extreme temperature of
discharged air
3. Plate heat exchanger
Check the water quality
Clean the plate heat exchanger
Seasonal protection measures
(anti-freeze in winter)
4. Fin heat exchanger
Clean the n heat exchanger
5. Others
Whether the Y-shaped lter needs to be cleaned
or replaced
Whether bolts have loosened
NOTE: THE PRECEDING MAINTENANCE PLAN IS FOR REFERENCE ONLY. THE MAINTENANCE PLAN MAY VARY BASED ON REGION.
● INDICATES ITEMS TO BE CHECKED BY CUSTOMERS; ▲ INDICATES ITEMS TO BE CHECKED BY SERVICE PERSONNEL.