EasyManua.ls Logo

Daikin UAL210A5 - Electrical Specifications; Safety Device Specifications

Daikin UAL210A5
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Electrical Data
Model UAL160A5 UAL210A5
Fan motor
Rated running current
208V~230V/3Ph/60Hz
A
4.5×2 6.5×2
460V/3Ph/60Hz
2.2×2 2.6×2
380V/3Ph/60Hz
4×2 4×2
Motor output W
1000×2 1000×2
Poles
6 8
Fan speed
208V~230V/3Ph/60Hz
RPM
910 910
460V/3Ph/60Hz
910 840
380V/3Ph/60Hz
690 690
Compressor
Rated running current
208V~230V/3Ph/60Hz
A
32.9 45.7
460V/3Ph/60Hz
17.9 19.2
380V/3Ph/60Hz
21.4 26.4
Locked rotor AMP (LRA)
208V~230V/3Ph/60Hz
A
267 304
460V/3Ph/60Hz
142 147
380V/3Ph/60Hz
160 168
IP/ Insulation grade
IPX4/E IPX4/E
Unit operating current
208V~230V/3Ph/60Hz
A
64.1 81.5
460V/3Ph/60Hz
32.7 40
380V/3Ph/60Hz
39 50
Unit max running current
208V~230V/3Ph/60Hz
A
79.1 103
460V/3Ph/60Hz
38.6 50
380V/3Ph/60Hz
49.1 65
NOTES:
1. ALL SPECIFICTIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2. MAX RUNNING CURRENT IS TESTED UNDER BELOW CONDITION: COOLING OUTDOOR DRY-BULB TEMPERATURE 43°C, HEATING
DRY-BULB TEMPERATURE 21°C, WET-BULB TEMPERATURE 15.5°C.
3. THE RATED RUNNING CURRENT ARE TESTED AT THE HIGH SPEED AND LOW SPEED.
Safety Devices
Model UAL160A5 UAL210A5
Safety device
High pressure switch
Type
PSW,H20PS B PSW,H20PS B
Open MPa
4.15 ± 0.1 4.15 ± 0.1
Close MPa
3.11 ± 0.1 3.11 ± 0.1
Low pressure switch
Type
N/A N/A
Open MPa
N/A N/A
Close MPa
N/A N/A
Phase sequencer
YES YES
Discharge temperature setting °C/°F
130/266 130/266
NOTE:
1. ALL SPECIFICTIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

Related product manuals