12
Heating capacity and heating power input performance table
UWL040B5
Using side LWT(ºC)
25 28 30 33 36 40 45 48 50
Capacity (kW)
Heat
source
EWT(ºC)
10 153.6 154.8 155.3 155.8 155.7 154.9 152.7 150.7 149.2
13 166 166.9 167.3 167.5 167.1 165.9 163.3 161 159.3
15 173.9 174.7 174.9 174.9 174.4 172.9 170 167.5 165.6
17 181.5 182.1 182.2 182 181.3 179.6 176.3 173.7 171.7
18 185.2 185.7 185.8 185.5 184.7 182.9 179.4 176.7 174.7
20 192.4 192.7 192.7 192.2 191.2 189.1 185.4 182.5 180.3
23 202.7 202.7 202.4 201.7 200.4 198 193.8 190.6 188.2
25 209.1 209 208.6 207.6 206.2 203.5 199 195.7 193.2
27 215.3 214.9 214.4 213.3 211.7 208.8 203.9 200.4 197.8
30 224 223.4 222.7 221.3 219.4 216.1 210.8 207 204.2
UWL040B5
Using side LWT(ºC)
25 28 30 33 36 40 45 48 50
Power (kW)
Heat
source
EWT(ºC)
10 21.3 23.8 25.5 27.9 30.4 33.7 37.9 40.4 42
13 21.7 24.2 25.8 28.2 30.6 33.9 37.9 40.3 42
15 22 24.4 26 28.4 30.8 34 38 40.4 42
17 22.4 24.7 26.3 28.6 31 34.1 38 40.4 41.9
18 22.5 24.8 26.4 28.7 31.1 34.2 38.1 40.4 42
20 22.9 25.1 26.7 29 31.3 34.3 38.1 40.4 42
23 23.4 25.6 27.1 29.3 31.6 34.6 38.3 40.5 42
25 23.8 26 27.4 29.6 31.8 34.8 38.4 40.6 42.1
27 24.2 26.3 27.8 29.9 32.1 35 38.6 40.7 42.2
30 24.8 26.9 28.3 30.4 32.5 35.3 38.8 40.9 42.3
Note: The parameters are tested base on unit rated water ow.