H3
Example 2.3
Indoor unit
Refnet joint
Refnet header
Outdoor multi con-
nection piping kit
Difference in height between outdoor and indoor units: H1.
Difference in height between indoor and indoor units: H2.
Difference in height between outdoor and outdoor units: H3.
Difference in height between outdoor and BP unit: H4.
Difference in height between BP unit and BP unit: H5.
Difference in height between BP unit and Mini-split indoor unit: H6.
Example 3: with standard multi layout
r st
Maximum allowable length
r Between outdoor and indoor units (standard multi/free multi combinations)
Actual piping
length
540 ft.
(165 m)
Example 1.1
unit 8: a+b+c+d+e+f+g+pd540 ft. (165 m)
Example 2.1
unit 8: a+b+c+d+e+f+g+pd540 ft. (165 m)
Example 1.2
unit 6: a+b+hd540 ft. (165 m)
unit 8: a+i+kd540 ft. (165 m)
Example 1.3
unit 8: a+id540 ft. (165 m)
Equivalent length
(2)
623 ft.
(190 m)
———
Total piping length 3280 ft.
(1000 m)
Example 1.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+pd3280 ft. (1000 m)
Example 2.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+pd3280 ft. (1000 m)
Example 1.2
a+b+c+d+e+f+g+h+i+j+k
d3280 ft. (1000 m)
Example 1.3
a+b+c+d+e+f+g+h+I
d3280 ft. (1000 m)
r Between outdoor branch and outdoor unit
QPN[KPECUGűV[RG
Actual piping
length
33 ft. (10 m) Example 3
rd33 ft. (10 m)
sd33 ft. (10 m)
td33 ft. (10 m)
Equivalent length 43 ft. (13 m)
—
Maximum allowable height difference
H1
d164 ft. (50 m ) (130 ft. (40 m)
(a)
(if outdoor is located below indoor units))
H2
d98 ft. (30 m)
H3
d16 ft. (5 m)
(a) %QPFKVKQPCNGZVGPUKQPWRVKNNHVOKURQUUKDNGYKVJQWVCFFKVKQPCNQRVKQP
kit:
+PECUGVJGQWVFQQTNQECVKQPKUJKIJGTVJCPKPFQQTGZVGPUKQPKURQUUKDNGWRVKNN
HVOCPFHQNNQYKPIEQPFKVKQPUOWUVDGHWNƂNNGF
Liquid piping size up (see table Size up for equivalent length for outdoor-
KPFQQTWPKVUQXGTHVOQPRCIG|
&GFKECVGFUGVVKPIQPQWVFQQTWPKVKUTGSWKTGFUGG=?QPRCIG|
+PECUGVJGQWVFQQTNQECVKQPKUNQYGTVJCPKPFQQTGZVGPUKQPKURQUUKDNGWRVKNN
|HVOCPFHQNNQYKPIEQPFKVKQPUOWUVDGHWNƂNNGF
130-197 ft. (40-60 m): minimum connection ratio connected: 80%.
197-213 ft. (60-65 m): minimum connection ratio connected: 90%.
213-262 ft. (65-80 m): minimum connection ratio connected: 100%.
262-295 ft. (80-90 m): minimum connection ratio connected: 110%.
Liquid piping size up (see table Size up for equivalent length for outdoor-indoor
WPKVUQXGTHVOQPRCIG|
&GFKECVGFUGVVKPIQPQWVFQQTWPKVKUTGSWKTGFUGG=?QPRCIG|