Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
1
1
VRV Systems • Outdoor Units
3
1 Specifications
Safety devices PC board fuse HPS HPS HPS HPS HPS
Inverter overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
HPS Over current
relay
Over current
relay
Over current
relay
Over current
relay
Over current
relay
Fan motor driver
overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Over current
relay
PC board fuse PC board fuse PC board fuse PC board fuse PC board fuse
Standard
Accessories
Standard Accessories Installation manual
Quantity 111111
Standard Accessories Operation manual
Quantity 111111
Standard Accessories Connection pipes
Quantity 444444
Notes Nominal cooling capacities are based on : indoor temperature : 27×CDB, 19×CWB, outdoor temperature : 35×CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20×CDB, outdoor temperature :CDB, 6×CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound pressure Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound values The refrigerant
charge of the
system must be
less than 100 kg.
This means that
in case the
calculated
refrigerant
charge is equal to
or more than 95
kg, you must
divide your
multiple outdoor
system into
smaller
independent
systems, each
containing less th
Sound values are measured in a semi-anechoic room.
1-2 TECHNICAL SPECIFICATIONS RXYHQ26P8W1B RXYHQ28P8W1B RXYHQ30P8W1B RXYHQ32P8W1B RXYHQ34P8W1B RXYHQ36P8W1B
Capacity Cooling kW 71.40 77.00 82.50 89.00 94.00 98.00
Heating kW 81.50 88.00 94.00 102.00 107.00 113.00
COPCooling 4.094.123.963.993.853.89
Heating 4.344.444.314.404.294.37
Capacity range HP 26 28 30 32 34 36
Power input
(nominal)(50Hz
)
Cooling kW 17.46 18.69 20.83 22.31 24.42 25.19
Heating kW 18.78 19.82 21.81 23.18 24.94 25.86
PED category Category II
Max n× of indoor units to be connected 42 45 48 52 55 58
Indoor index
connection
Minimum 325 350 375 400 425 450
Maximum 845 910 975 1,040 1,105 1,170
Casing Colour Daikin White
Material Painted galvanised steel
1-2 TECHNICAL SPECIFICATIONS RXYHQ12P8W1B RXYHQ16P8W1B RXYHQ18P8W1B RXYHQ20P8W1B RXYHQ22P8W1B RXYHQ24P8W1B