Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
1
1
VRV Systems • Outdoor Units
5
1 Specifications
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Capacity Control ~ 100
Safety devices HPS
Fan motor driver overload protector
Over current relay
Inverter overload protector
PC board fuse
Standard
Accessories
Standard Accessories Installation manual
Quantity 111111
Standard Accessories Operation manual
Quantity 111111
Standard Accessories Connection pipes
Quantity 444444
Notes Nominal cooling capacities are based on : indoor temperature : 27×CDB, 19×CWB, outdoor temperature : 35×CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20×CDB, outdoor temperature :CDB, 6×CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant
charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent
systems, each containing less th
1-3 ELECTRICAL SPECIFICATIONS
(50HZ)
RXYHQ12P8W1B RXYHQ16P8W1B RXYHQ18P8W1B RXYHQ20P8W1B RXYHQ22P8W1B RXYHQ24P8W1B
Power Supply Name W1
Phase 3N~
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Current Nominal
running current
(RLA)
Cooling A 19.1 15.0 18.8 26.6 30.4 22.5
Heating A 12.9 16.4 19.3 21.1 24.0 24.6
Starting current (MSC) A 75 4 78 79 88 7
Z-max Text 0.27 - 0.27 0.27 0.25 -
Minimum Ssc value kVa 1,114 2,436 2,146 2,332 2,042 3,654
Minimum circuit amps
(MCA)
A 22.7 37.0 40.1 41.2 44.3 55.5
Maximum fuse amps (MFA) A 25 50 50 50 50 63
Full load amps (FLA) A 1.2 1.4 1.6 1.9 2.1 2.1
Voltage range Minimum V 360 360 360 360 360 360
Maximum V 440 440 440 440 440 440
Wiring
connections
For Power
Supply
Quantity 5 5 5 5 5 5
Remark Earth wire include
For connection
with indoor
Quantity 2 2 2 2 2 2
Remark F1-F2
Power Supply Intake Both indoor and outdoor unit
1-2 TECHNICAL SPECIFICATIONS RXYHQ26P8W1B RXYHQ28P8W1B RXYHQ30P8W1B RXYHQ32P8W1B RXYHQ34P8W1B RXYHQ36P8W1B