Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
2 Electrical data
RXYHQ-P
NOTES
1 In accordance with EN/IEC 61000-3-11
(1)
, respectively EN/IEC 61000-3-11
(2)
, it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Z
sys
(4)
Z
max
, respectively S
sc
(3)
minimum S
sc
value
2
(1)
European/International technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated 75A.
(2)
European/International technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current 16A and 75A per phase .
(3)
Short-circuit power
(4)
System impedance.
Combination of
Minimum Ssc value
[kVA]
Zmax
[
]
RXYHQ12 1114 0.27
RXYHQ16 RXYQ8 + RXYQ8 2436 -
RXYHQ18 RXYQ8 + RXYQ10 2146 0.27
RXYHQ20 RXYQ8 + RXYHQ12 2332 0.27
RXYHQ22 RXYQ10 + RXYHQ12 2042 0.25
RXYHQ24 RXYQ8 + RXYQ8 + RXYQ8 3654 -
RXYHQ26 RXYQ8 + RXYQ8 + RXYQ10 3364 0.27
RXYHQ28 RXYQ8 + RXYQ10 + RXYQ10 3074 0.25
RXYHQ30 RXYQ8 + RXYQ10 + RXYHQ12 3260 0.25
RXYHQ32 RXYQ8 + RXYHQ12 + RXYHQ12 3446 0.25
RXYHQ34 RXYQ10 + RXYHQ12 + RXYHQ12 3156 0.24
RXYHQ36 RXYHQ12 + RXYHQ12 + RXYHQ12 3342 0.24