1 Specifications
1-3 ELECTRICAL SPECIFICATIONS
(50HZ)
RXYHQ26P8W1B RXYHQ28P8W1B RXYHQ30P8W1B RXYHQ32P8W1B RXYHQ34P8W1B RXYHQ36P8W1B
Power Supply Name W1
Phase 3N~
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Current Nominal
running current
(RLA)
Cooling A 26.3 30.1 37.9 45.7 49.5 57.3
Heating A 27.5 30.4 32.2 34.0 36.9 38.7
Starting current (MSC) A 82 91 91 92 101 101
Z-maxText 0.270.250.250.250.240.24
Minimum Ssc value kVa 3,364 3,074 3,260 3,446 3,156 3,342
Minimum circuit amps
(MCA)
A 58.6 61.7 62.8 63.9 67.0 68.1
Maximum fuse amps (MFA) A 80 80 80 80 80 80
Full load amps (FLA) A 2.3 2.5 2.8 3.1 3.3 3.6
Voltage range Minimum V 360 360 360 360 360 360
Maximum V 440 440 440 440 440 440
Wiring
connections
For Power
Supply
Quantity 5 5 5 5 5 5
Remark Earth wire include
For connection
with indoor
Quantity 2 2 2 2 2 2
Remark F1-F2
Power Supply Intake Both indoor and outdoor unit
Notes MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27×CDB/19×CWB , outdoor temperature : 35×CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or
above listed range limits
In accordance with EN/IEC 61000-3-11(1), respectively EN/IEC 61000-3-12(2), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a supply with Zsys(4) <= Zmax,
respectively Ssc(3) >= minimum Ss
Select wire size based on MCA