www.DaikinApplied.com 49 IOM 1322 • WATER-COOLED SCROLL COMPRESSOR
Inputs/Outputs
Table 41: Analog Inputs
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrig. Dependent
NOTE: 1. If Water Cooled = Y, then Entering Condenser. If Water Cooled = N, then Outside Ambient.
NOTE: 2. Selection of R134a in unit setpoint screen will modify unit operation for Templier application.
Table 42: Analog Outputs
# Description Output Signal Range
1 Cooling Tower Bypass Valve Position 0 to 10 VDC 0 to 100% Open
2 Cooling Tower VFD Speed 0 to 10 VDC 0 to 100%
3 Circuit #1 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
4 Circuit #2 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
NOTE: Analog outputs 3 & 4 are for R410A and R134a units
only.