www.DaikinApplied.com 79 IOM 1322 • WATER-COOLED SCROLL COMPRESSOR
• ICE w/GLYCOL, used with ice storage systems,
allows changing from chilled glycol operation to lower
temperature ICE operation. In ICE, the unit runs at full
load until the ICE setpoint is reached, at which time the
unit shuts o. A three-position switch wired to terminals
#28 and #38 initiates the change from glycol cooling to
making ice. (See wiring diagrams on page 8 or 9.)
Unit Mode settings can be COOL COOLw/Glycol, or ICEw/
Glycol, as determined from the Unit Mode setpoint.
Source settings can be KEYPAD, SWITCHES, or NETWORK
as determined from the Mode Source setpoint.
SET UNIT SPs (2)
Available Modes
SET UNIT SPs (3)
SET UNIT SPs (4)
See page 13 for an explanation of compressor staging.
SET UNIT SPs (5)
SET UNIT SPs (5)
Evap Pump choices are; #1 Only, #2 Only, Auto, #1 Primary, #2
Primary.
SET UNIT SPs (6)
SET UNIT SPs (6)
TGZ Units (R134a)
SET UNIT SPs (6)
is the setting for units with on-board
water-cooled condensers. Pump choices are;
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary.
is used for units with remote condensers,
usually air cooled.
SET UNIT SPs (7)
H.G. Delay, hot gas bypass delay, keeps the hot gas solenoid
valve closed when the rst compressor on a
circuit starts. This delay allows sucient condenser pressure to
build up.
SET UNIT SPs (8)
CLOCK
hh:mm:ss
SET UNIT SPs (9)
SET UNIT SPs (9)
Refrigerant type is factory-set.
SET UNIT SPs (10)
BAS interface settings, available mid-2003.