IOM 1322 • WATER-COOLED SCROLL COMPRESSOR 80 www.DaikinApplied.com
SET UNIT SPs (11)
Evap Press Sensor
The pressure osets on menus 11 and 12 and the temperature
osets on menus 10, 11 and 12 correct the controller’s display
of the parameters. The sensors used in these units have a high
degree of repeatability but may need correction (oset). An
accurate pressure gauge or thermometer is used to determine
the correct temperature or pressure. A positive or negative
oset value is then entered to make the controller reading
agree with the measured value.
SET UNIT SPs (12)
Cond Press Sensor
SET UNIT SPs (13)
Evap Leaving Water
Temperature Sensor
SET UNIT SPs (13)
LWT Sensors
SET UNIT SPs (14)
OAT/Cond Lvg Water
Temperature Sensor
SET UNIT SPs (14)
LWT Sensors
SET UNIT SPs (15)
Suction Temp Sensor
WGZ Unit (R410A)
SET UNIT SPs (16)
SET UNIT SPs (16)
Liq Line Temp Sensors
Circ1 Oset = 00.0 ºF
Circ2 Oset = 00.0 ºF
WGZ Unit (R410A)
SET UNIT SPs (17)
ENTER PASSWORD: XXXX
Active Password
Level: None
SET UNIT SPs (17)
TGZ Unit in Cooling Mode
SET UNIT SPs (17)
ENTER PASSWORD: XXXX
Active Password
Level: None
TGZ Unit in Heat Mode
SET UNIT SPs (17)
TGZ Unit Heat Mode
SET UNIT SPs (18)
ENTER PASSWORD: XXXX
Active Password
Level: None
Two four-digit passwords provide OPERATOR and MANAGER
levels of access to changeable parameters. The passwords
are preprogrammed into the controller. Either password must
be entered using the ENTER PASSWORD (12) screen before
a protected setting can be changed. The operator password is
0100. The manager level is 2001.