www.DaikinApplied.com 95 IOM 1322 • WATER-COOLED SCROLL COMPRESSOR
Step 2: Once steady state minimum desired operating ow is
obtained, perform the ‘Teach’ function on the ow switch. The
‘Teach’ function is initiated by holding down the minus ‘-’ button
on the face of the ow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the
‘Teach’ function is completed, the outer LEDs will ash green
as shown in Figure 46.
Figure 46: Automatic Teach of Setpoint
Table 46: Flow Volume Calculation
Step 3: After the ‘Teach’ function is completed and the outer
LEDs ashed, the ow switch will indicate a new set point
based upon the current ow which should still be at the steady
state minimum desired operating ow.Figure 47 shows a
typical display for this condition. All LEDs to the left of the
SP LED are lit green. The SP LED is lit RED (or may toggle
amber) which indicates that the ow switch is OPEN. Typically,
an increase in uid ow is between 15% to 30% above the
‘Teach’ function ow is required for the SP LED to turn AMBER
and the ow switch to CLOSE indicating acceptable ow.
Figure 47: Teach Adjustment Complete
