Air Conditioner Service Manual
54
3.2.15 P8---Outdoor Overtemperature/Under-temperature protection
When environment temperature as below condition, the compressor will stop working, after 200s delay, the IDU will
show P8 failure code.
(1). On Cooling or Dry mode: ODU ambient temperature: OAT<-20℃ or OAT>63℃;
(2). On Heating mode:
a. OAT≥40℃ or
b. 30℃<OAT≤40℃ and RT>35℃
Ambient
temperature under
spec. range?
No enough space for
ODU ventilation?
The sensor open
or short circuit?