Dametric AB BRM-DM1/2 User manual
BRM-DM12 UM EN.docx Feb. 18, 2020 Page 7 of 10
5.6 Control motor
CMD Off/On/On+Al Off=disconnected, On=connected, On+Alarm=connected to the sum alarm function.
CMD Screw pitch Thread, set thread pitch in mm for the control rod (mm).
CMD Low speed Rotor travel speed at low speed (mm/s).
CMD High speed Rotor travel speed at high speed (mm/s)
CMD Direction Direction, set 0 or 1.
CMD Drive curr. Drive current (A).
CMD Hold curr. Hold current (A).
CMD Min hold cu. Min limit for the current consumption in hold mode (A).
CMD Run current Actual current consumption (A).
5.7 Hydr.pressure. A
The parameters are valid for the hydraulic pressure measurement for control apart.
HPA Off/On/On+Al Off=disconnected, On=connected, On+Alarm=connected to the sum alarm function.
HPA Al.lim.1 HH Alarm limit 1, high-high (ton).
HPA Al.lim.2 H Alarm limit 2, high (ton).
HPA Range Range (ton).
HPA Zero calibr. Zero calibration, se calibration manual for actual measure system.
HPA Span calibr. Span calibration, se calibration manual for actual measure system.
5.8 Hydr.pressure. B
The parameters are valid for the hydraulic pressure measurement for control together.
Same as above but ”HPA” is replaced by ”HPB”.
5.9 Temp fr. Bearing
The parameters are valid for the temperature measurement on the oil from the bearing.
OT1 Off/On/On+Al Off=disconnected, On=connected, On+Alarm=connected to the sum alarm function.
OT1 Al.lim. 1HH Alarm limit 1, high-high (ºC).
OT1 Al.lim. 2H Alarm limit 2, high (ºC).
OT1 Zero calibr. Zero calibration, se calibration manual for actual measure system.
OT1 Span calibr. Span calibration, se calibration manual for actual measure system.
5.10 Temp to Bearing
The parameters are valid for the temperature measurement on the oil to the bearing.
Same as above but ”OT1” is replaced by ”OT2”.
5.11 Main motor power
MPM Off/On/On+Al Off=disconnected, On=connected, On+Alarm=connected to the sum alarm function.
MPM Al.lim. 1LL Alarm limit 1, low-low (MW).
MPM Al.lim. 2L Alarm limit 2, low (MW).
MPM Al.lim. float Alarm limit, floating, level (MW).
MPM Al.lim. filt. Alarm limit, floating, filter time (s).
MPM Range Range (MW).
MPM Type Type, set 1.
MPM Zero calibr. Zero calibration, se calibration manual for actual measure system.
MPM Span calibr. Span calibration, se calibration manual for actual measure system.