Illustration 5.2: For control cable connections, see section on
Control Terminals
.
5.1.5 PC software tools
PC-based Configuration Tool MCT 10
All Frequency converters are equipped with a serial communication port. Danfoss provides a PC tool for communication between PC and frequency
converter, PC-based Configuration Tool MCT 10. Please check the section on
Available Literature
for detailed information on this tool.
MCT 10 set-up software
MCT 10 has been designed as an easy to use interactive tool for setting parameters in our frequency converters. .
The MCT 10 set-up software will be useful for:
Planning a communication network off-line. MCT 10 contains a complete frequency converter database
Commissioning frequency converters on line
Saving settings for all frequency converters
Replacing a frequency converter in a network
Simple and accurate documentation of frequency converter settings after commissioning.
Expanding an existing network
Future developed frequency converters will be supported
MCT 10 set-up software supports Profibus DP-V1 via a Master class 2 connection. It makes it possible to on line read/write parameters in a frequency
converter via the Profibus network. This will eliminate the need for an extra communication network.
Save frequency converter settings:
1. Connect a PC to the unit via USB com port. (Note: Use a PC, which is isolated from the mains, in conjunction with the USB port. Failure to do
so may damage equipment.)
2. Open MCT 10 Set-up Software
3. Choose “Read from drive”
4. Choose “Save as
All parameters are now stored in the PC.
ADAP-KOOL
®
Drive AKD 102 High Power 5 How to Operate the Frequency Converter
MG.11.O1.02 - ADAP-KOOL
®
is a registered Danfoss trademark
61