3-03 Maximum Reference
Range: Function:
50.000 Ref-
erenceFeed-
backUnit*
[par. 3-02 - 999999.999 Referen-
ceFeedbackUnit]
Enter the maximum acceptable value for the remote reference. The Maximum Reference value and
unit matches the configuration choice made in par.1-00
Configuration Mode
and par. 20-12
Refer-
ence/Feedback Unit
, respectively.
NB!
If operating with par.1-00
Configuration Mode
set for Closed Loop [3],
par. 20-14
Maximum Reference/Feedb.
must be used.
3-41 Ramp 1 Ramp Up Time
Range: Function:
10.00 s* [1.00 - 3600.00 s] Enter the ramp-up time, i.e. the acceleration time from 0 RPM to par.1-25
Motor Nominal Speed
.
Choose a ramp-up time such that the output current does not exceed the current limit in
par. 4-18
Current Limit
during ramping. See ramp-down time in par.3-42
Ramp 1 Ramp Down
Time
.
par
.3 41 =
tacc
×
nnorm
par
.1 25
ref
rpm
s
3-42 Ramp 1 Ramp Down Time
Range: Function:
20.00 s* [1.00 - 3600.00 s] Enter the ramp-down time, i.e. the deceleration time from par.1-25
Motor Nominal Speed
to 0 RPM.
Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
in par. 4-18
Current Limit
. See ramp-up time in par.3-41
Ramp 1 Ramp Up Time
.
par
.3 42 =
tdec
×
nnorm
par
.1 25
ref
rpm
s
3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0] * Linked to Hand / Auto Use local reference when in Hand mode; or remote reference when in Auto mode.
[1] Remote Use remote reference in both Hand mode and Auto mode.
[2] Local Use local reference in both Hand mode and Auto mode.
NB!
When set to Local [2], the frequency converter will start with this setting again
following a 'power down'.
5-10 Terminal 18 Digital Input
Option: Function:
[0] No operation No reaction to signals transmitted to terminal.
[1] Reset Resets frequency converter after a TRIP/ALARM. Not all alarms can be reset.
[2] Coast inverse Leaves motor in free mode. Logic ‘0’ => coasting stop.
(Default Digital input 27): Coasting stop, inverted input (NC).
[3] Coast and reset inverse Reset and coasting stop Inverted input (NC).
Leaves motor in free mode and resets the frequency converter. Logic ‘0’ => coasting stop and reset.
[5] DC-brake inverse Inverted input for DC braking (NC).
Stops motor by energizing it with a DC current for a certain time period. See par. 2-01
DC Brake
Current
to par. 2-03
DC Brake Cut In Speed [RPM]
. The function is only active when the value in
par. 2-02
DC Braking Time
is different from 0. Logic ’0’ => DC braking.
6 How to Programme the Frequency Converter ADAP-KOOL
®
Drive AKD 102 High Power
72
MG.11.O1.02 - ADAP-KOOL
®