16 Manual RS8GE202 © Danfoss 01-2016 AK-PC 560
Operating hours of relay 8 (value time 1000) o53 0.0 h 99.9 h 0.0
Selection of application
1. Show temperature and "c16" mode
2: Show pressure and "c16" mode
o61 1 2 1 2 1
Function for relay output DO9:
0. Start / stop of speed regulation
1. Inject on signal for evaporator control
2. Boost ready (at least one compressor is on)
3. Start /stop of condenser fan
o75 0 3 0
Function for relay output DO10:
0. Alarm relay
1. Start / stop of condenser fan
o76 0 1 0
Denition of alarm message at DI1 signal:
0. Not used
1. Fan failure (A34)
2. DI1 alarm (A28)
o78 0 2 0
Display connection
O: EKA 164
On: EKA 165 (extended display with light-emitting diodes)
o82 O On O
Service
Temperature at Saux (discharge gas temperature) u03
Status on DI1 input u10
Status on DI2 input u37
Read temperature at sensor "Sc3" u44 °C
Read temperature at sensor "Sc4" u45 °C
Status on DI3 input u87
Status on DI4 input u88
Status on DI5 input u89
Read regulation capacity in % of the digital scroll U28