EasyManua.ls Logo

Danfoss AKS 4100 - Page 4

Danfoss AKS 4100
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enter menu system
Enter QUICK SETUP
Unit change at
distance/level
readout:
m, cm, mm, in, ft
Change between:
Distance*
Level**
Output (%)***
Output (mA)****
4-20 mA output displayed as bar graph
and in percentage [%]
Measurement name (in this example,
DISTANCE)
Device tag name
Measurement reading and unit
Device status (markers)
1 = Hardware problem (any hardware
problem making the device unable to
provide a correct measurement
(communication, memory problem…)
2 = No Reference Pulse
3 = Low Voltage or Measurement Old
4 = Level Lost
Keypad buttons
Flashing star indicating unit in operation.
* DISTANCE is a display option.
If the display is set to “DISTANCE” the displayed
value will be the distance from the Reference
point to the top surface of the liquid refrige-
rant (see g. 5).
** LEVEL is display option.
If the display is set to “LEVEL then the value
displayed will be:
PROBE LENGTH (entered in QUICK SETUP)
– DISTANCE (see g. 5).
*** OUTPUT (%) is display option.
Will represent the level of refrigerant,in
percent, scaled (entered in QUICK SETUP)
according to: SCALE 4 mA (0%), SCALE
20 mA (100%) (see g. 5).
**** OUTPUT I (mA) is display option.
Will represent the level of refrigerant,in 4-20
milliampere, scaled (entered in QUICK
SETUP) according to: SCALE 4 mA (4 mA),
SCALE 20 mA (20 mA) (see g. 5).
4 DKRCI.PI.SC0.D2.02 / 520H5637 © Danfoss A/S (AC-SMC/MWA), 01-2012
AKS 4100/4100U
connected to PLC
Fig. 11
*
AKS 4100
Fig. 12
+
AKS 4100/4100U
+
Active
Analog Input 4-20 mA
14-30 V d.c.
PLC
Danfoss
M84H0020_1

Other manuals for Danfoss AKS 4100

Related product manuals