6 DKRCI.PI.SC0.E5.02 / 520H5658 © Danfoss A/S (AC-MCI/MWA), 11-2013
• Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press 3 times.
• Press
• Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D14 and press to confirm.
• Press (YES) to confirm
• Press to change GAS EPS.R.
(Select the correct value from the tables
on page 8)
Press to change cursor-
position.
Press
to decrease the value or
to
increase the value.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press to confirm.
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to confirm.
• Press
or
to select between
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
You have the possibility of checking
your settings by pressing
twice.
Press
to return to
default screen.
Quick Setup (all values below are only examples)
• Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press 3 times.
• Press
• Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D14 and press to confirm.
• Press
(NO) to confirm
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to confirm.
• Press
or
to select between
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
5000 mm
When CO
2
is used:
For all other refrigerants:
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
LENGTH
05000 mm
Note:
The signal converter can be programmed with or without mechanical process connector assembled.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
COAXIAL 2200 mm
(0 %) 4 mA 1900 mm
(100 %) 20 mA 70 mm
D14