6  DKRCI.PI.SC0.E5.02 / 520H5658  © Danfoss A/S (AC-MCI/MWA), 11-2013
•   Connect the device to the power supply 
  (see the section "Electrical installation/ 
 connection").
•   Press   3 times.
•   Press   
•   Press 
 
or 
 
to select between SINGLE,  
  COAXIAL D14 and COAXIAL D22. Choose  
  COAXIAL D14 and press    to confirm. 
•   Press   (YES) to confirm
•   Press   to change GAS EPS.R. 
  (Select the correct value from the tables  
  on page 8) 
 Press   to change cursor- 
 position. 
  Press 
 
to decrease the value or 
 
to 
  increase the value.
AKS 4100
QUICK SETUP ?
YES                  NO
AKS 4100
PROBE TYPE
SINGLE CABLE
•   Press   to confirm.
•   Press 
 
to change the PROBE LENGTH. 
 Press 
 
to change the position of the  
 cursor.  
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm. 
•   Press 
 
to change of SCALE 4 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm. 
•   Press 
 
to change of SCALE 20 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm.
•   Wait for QUICK SETUP to complete.  
  Count down from 8 sec.
•   Press   to confirm.
•   Press 
 
or 
 
to select between  
  STORE NO or STORE YES.  
 Press   to confirm. 
  Default screen appears:
  Quick Setup completed
  You have the possibility of checking 
  your settings by pressing 
 
twice.
 Press   
 
  to return to 
  default screen.
Quick Setup (all values below are only examples)
•   Connect the device to the power supply 
  (see the section "Electrical installation/ 
 connection").
•   Press   3 times.
•   Press   
•   Press 
 
or 
 
to select between SINGLE,  
  COAXIAL D14 and COAXIAL D22. Choose  
  COAXIAL D14 and press   to confirm.
•   Press 
 
(NO) to confirm
AKS 4100
QUICK SETUP ?
YES                  NO
AKS 4100
PROBE TYPE
SINGLE CABLE
•   Press 
 
to change the PROBE LENGTH. 
 Press 
 
to change the position of the  
 cursor.  
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm. 
•   Press 
 
to change of SCALE 4 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm. 
•   Press 
 
to change of SCALE 20 mA. 
 Press 
 
to change the cursor position. 
 Press 
 
to decrease the value or 
 
to 
  increase the value. 
 Press   to confirm.
•   Wait for QUICK SETUP to complete.  
  Count down from 8 sec.
•   Press   to confirm.
•   Press 
 
or 
 
to select between  
  STORE NO or STORE YES.  
 Press   to confirm. 
  Default screen appears:
  Quick Setup completed
AKS 4100
PROBE  LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP 
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
5000 mm
When CO
2
 is used:
For all other refrigerants:
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP 
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
LENGTH
05000 mm
Note: 
The signal converter can be programmed with or without mechanical process connector assembled.
AKS 4100
QUICK SETUP ?
YES                     NO
AKS 4100
QUICK SETUP ?
YES                     NO
AKS 4100
COAXIAL 2200 mm
(0 %) 4 mA 1900 mm
(100 %) 20 mA 70 mm
D14