Fan Size
Item Number
20x20mm
1E51590C
90x90mm
1E250102C
120mmx120mm
1E51335C
b.
Water cooled systems
Unplug the water pump and restart the compressor to confirm the compressor will
now run.
If the system now runs it means the pump is drawing more than 1 Amp. The
system should be set up with the pump connected via a relay or pump interface
to
prevent t
his happening
.
If it is not, add a relay to the system or contact Penguin Refrigeration for
further details.
If there is a relay/pump interface already fitted it may have developed a fault.
Again please
contact Penguin Refrigeration for further details.
3
Flashes
Compressor Start Error
This could still be a voltage error, due to a power surge or similar, or a faulty
compressor controller.
First turn off the power to the unit for 1 minute to let the system reset. Turn the
power back on and see if the fridge runs.
If the system still fails to start either:
Return the control box to Penguin Refrigeration for testing
Replace electronic controller:
1E50895
http://www.penguinfrigo.co.uk/products/Electronic_Unit_for_Danfoss_BD35_Compressors
-
185
-
37.html
4
Flash
es
Compressor Overload
Send the controller to Penguin Refrigeration for testing, or contact our technical
team for further assistance.
5
Flash
es
Compressor Overload
Send the controller to Penguin Refrigeration for testing, or contact our technical
team for further assistance.