EasyManua.ls Logo

Danfoss DHP-H Opti Pro

Danfoss DHP-H Opti Pro
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.5 Sub-menu INSTALLATION
Table 21. Used for settings that are set during installation.
Menu selection Meaning Factory setting
SYSTEM Sub menu SERVICE -> INSTALLATION -> SYSTEM:
Note! The menu selection in the SYSTEM menu varies depending on the selected
values. Tip: start in the top menu and work downwards.
Menu selection Meaning
HEAT SOURCE GROUND OR ROCK
OUTSIDE AIR
(BRINE SOLUTION, DIRECT EVAP.)
COOLING PASSIVE COOLING
( , EXTERNAL, INTEGRATED IN HP)
COOLING A
( , EXTERNAL)
ROOM SENSOR
( , ON)
POOL
, ON
SHUNT GROUP
, ON
BUFFER TANK (See sepa-
rate instruction for buffer
tank)
BUFFER TANK
SYSTEM SHUNT
2ND H.C SHUNT
ADDITION OPTIMUM
( , ON)
HGW
( , ON)
0-10V
( , EXT. AUX. HEATER)
FLOW SENSOR
(
, ON)
CURRENT LIMITER
(
, ON)
PHASE FAULT
(
, PHASE READING)
SERVICE TIME
Note! Only used for test operation. The heat
pump counts 60 times as fast, which means that
the waiting times are eliminated during test
operation.
0 = deactivates SERVICE TIME
1 = activates SERVICE TIME, which speeds up the control sys-
tem’s integral calculation and start delay by 60 times.
-
58 – Installation instructions VMBMA1002

Table of Contents

Other manuals for Danfoss DHP-H Opti Pro

Related product manuals