InstallationGuideECLComfort210/310,applicationA214/A314
MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
Mrun(runningtimeofthemotorizedcontrolvalve)
1x186
CircuitSettingrange
Factorysetting
All
**
‘Mrunisthetimeinsecondsittakesthecontrolledcomponenttomove
fromfullyclosedtofullyopenposition.



Howtocalculatetherunningtimeofamotorizedcontrolvalve


Seatedvalves


Example:
5.0mmx15sec./mm=75sec.
Rotatingvalves


Example:90degr.x2sec./degr.=180sec.
MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.,fan
MENU>Settings>Controlpar.,inlet
MENU>Settings>Controlpar.,outlet
MENU>Settings>Controlpar.,Pcirc.
MENU>Settings>Controlpar.,Prell
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
Nz(neutralzone)
1x187
CircuitSettingrange
Factorysetting
All
**
Whentheactualow/ducttemperatureiswithintheneutralzone,the
controllerdoesnotactivatethemotorizedcontrolvalve.







MENU>Settings>Controlpar.
MENU>Settings>Controlpar.,cool.
MENU>Settings>Controlpar.1
MENU>Settings>Controlpar.2
Min.act.time(min.activationtimegearmotor)
1x189
CircuitSettingrange
Factorysetting
All
**
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear
motor.

SettingexampleValuex20ms







