16
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
When DanfossLink™ CC are used in conjunction with Online 2*, they can be integrated in the following two ways:
• System integration
• No system integration
“No system integration” is the default method during installation. When system integration is selected, Danfoss
Link
™ CC manages most functions in the heat pump. In this case, the functions controlled by Danfoss Link CC™ are
locked in relation to Online. The table below shows the relationship between disabled and enabled functions from
an Online perspective.
Tab Section Function System integr. No system
integr.
Status Indoor temperature (value: ROOM
(+/-)
No Yes
Details Heat curve Curve No Yes
Min No Yes
Max No Yes
+5 ºC No Yes
0 ºC No Yes
-5 ºC No Yes
Heat stop Yes Yes
Room factor No Yes
Danfoss DHP-AQ Calendar
control
Temperature decrease No Yes
Hot water block Yes Yes
Quiet mode Yes Yes
EVU mode Yes Yes
Yes Yes
Danfoss DHP-H, L Calendar
control
Temperature decrease No Yes
No = Function cannot be changed via Online when the system is in ”system integration”
Yes = Function can be changed Online regardless of whether system integration has been enabled or not
Using the Online application, you can change the integration options and go from “System integration” to “No
system integration” and take control of the function settings and vice versa.
Using Danfoss Link™ CC with Online 2
* The following does not apply to HP kits with product numbers: 086L2381 and 086L2382, as these are not
compatible with Online 2.