FRCC.EI.002.A3.02 © Danfoss Commercial Compressors 05/14
The compressor must only be used
for its designed purpose(s) and within
its scope of application (refer to «ope-
rating limits»).
Consult Application guidelines and da-
tasheet available from cc.danfoss.com
The compressor is delivered under
nitrogen gas pressure (between
0.3 and 0.7 bar) and hence can-
not be connected as is; refer to
the «assembly» section for further
details.
Under all circumstances, the
EN378 (or other applicable local
safety regulation) requirements
must be fullled.
The compressor must be han-
dled with caution in the vertical
position (maximum oset from
the vertical : 15°)
Operating limits
MT MTZ NTZ
R22 R417A R407A** R407C R407F** R134a R404A / R507 R404A / R507
160P 160PZ * 160PZ 160PZ 160PZ 160PZ 160PZ 160PZ
High side pressure range bar (g) 10.9 - 27.7 9.4 - 25.5 11.6 - 25.8 12.5 - 29.4 12.1 - 24 7.9 - 22.6 13.2 - 27.7 13.2 - 27.7
Low side pressure range bar (g) 1.0 - 7.0 0.55 - 5.7 0.90 - 5.94 1.4 - 6.6 0.99 - 6.25 0.6 - 4.7 1.0 - 7.2 0.1 - 3.3
Discharge temperature must be kept lower than 130°C
* When MT compressors are used with R417A, the factory charged mineral oil 160P must be replaced by polyolester oil 160PZ.
** R407A and R407F are not used for China Market.
C
E
D
A
B
F
1" : 80 Nm
1"1/4 : 90 Nm
1"3/4 : 110 Nm
Installation and servicing of the compressor by qualied personnel only. Follow these instructions and sound refrigeration engineering
practice relating to installation, commissioning, maintenance and service.
C
R
S
IOL
230 V
RC
TH
C
S
R
IOL
1 ~ PSC
1
~ CSR
3
~
230 V
SR
5
2
1
C
S
R
IOL
TH
RC
SC
C
R
S
Never operate compressors without
terminal cover tted
A: Model number D: Supply voltage, Starting current & Maximum current
B: Serial number E: Housing service pressure
C: Refrigerant F: Factory charged lubricant
TH : Thermostat
SR : Start Relay
SC : Start Capacitor
RC : Run Capacitor
IOL : Motor Protector
INSTRUCTIONS
MT / MTZ / NTZ COMPRESSORS