VFD500 high performance vector control frequency inverter user manual Chapter2 production information
2.3Technical Specifications
Table 2-2 VFD500 Technical Specifications
Single phase :220V ,50/60HZ
VFD500-R40GS2
1.3
6.0
3.2
5.6
0.4
SIZE A
Inbuil
t
VFD500-R75GS2
2.4
11.0
5.6
8.0
0.75
SIZE A
VFD500-1R5GS2
3.5
15.0
8.0
10.6
1.5
SIZE A
VFD500-2R2GS2
5.5
25.0
10.6
14.0
2.2
SIZE A
VFD500-4R0GS2
7.7
35.0
17.0
23.0
4.0
SIZE B
VFD500-5R5GS2
8.9
53.0
25.0
31.0
5.5
SIZE C
VFD500-7R5GS2
11
67.0
32.0
37.0
7.5
SIZE C
Model
Power
capacity
(KVA)
Input
current
(A)
Output current(A)
Adapta
ble
Motor
(KW)
SIZE
Brake
Unit
Heavy
load
Light
load
Three phase: 380-480V50/60Hz
VFD500-R75GT4B
1.5
3.4
2.5
4.2
0.75
SIZE A
Intern
al
VFD500-1R5GT4B
3
5
4.2
5.6
1.5
Item
Specifiation
Input
Inuput Voltage
1phase/3phase 220V200V240V
3 phase 380V-480V380V480V
Allowed
Voltage
fluctuation
range
-15%10%
Input frequency
50Hz / 60Hzfluctuation less than 5%
Output
Output Voltage
3phase0input voltage
Overload
capacity
General purpose application60S for 150% of the rated current
Light load application60S for 120% of the rated current
8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VFD500-015G/018PT4B and is the answer not in the manual?

Danfoss VFD500-015G/018PT4B Specifications

General IconGeneral
BrandDanfoss
ModelVFD500-015G/018PT4B
CategoryDC Drives
LanguageEnglish

Related product manuals