EasyManuals Logo

Danfoss VLT 2822 General Information

Danfoss VLT 2822
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
227
Warning: Low feedback, FB
LOW
(warn.feedb. low)
Value:
-100,000.000 - par. 228 Warn.:
FB
HIGH
-4000.000
Function:
If the feedback signal falls below the preset limit
FB
LOW
, a warning is given.
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and af-
ter a stop command or during stop. The warning func-
tions are activated when the output frequency has
reached the resulting reference.The signal outputs
can be programmed to give a warning signal via ter-
minal 46 and via the relay output.The unit for feedback
in Closed loop is programmed in parameter 416 Proc-
ess units.
Description of choice:
Set the required value within the feedback range (pa-
rameter 414 Minimum feedback, FB
MIN
and 415 Max-
imum feedback, FB
MAX
).
228
Warning: High feedback, FB
HIGH
(warn.feedb high)
Value:
Par. 227 Warn.: FB
LOW
- 100,000.000
4000.000
Function:
If the feedback signal gets above the preset limit
FB
HIGH
, a warning is given.
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and af-
ter a stop command or during stop. The warning func-
tions are activated when the output frequency has
reached the resulting reference. The signal outputs
can be programmed to give a warning signal via ter-
minal 46 and via the relay output. The unit for feedback
in Closed loop is programmed in parameter 416 Proc-
ess units.
Description of choice:
Set the required value within the feedback range (pa-
rameter 414 Minimum feedback, FB
MIN
and 415 Max-
imum feedback, FB
MAX
).
229 Frequency bypass, bandwidth
(FREQ BYPASS B.W.)
Value:
0 (OFF) - 100 Hz
0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of mechanical resonance problems
in the system. In parameters 230-231 Frequency by-
pass, these output frequencies can be programmed.
In this parameter, a bandwidth can be defined on either
side of these frequencies.
Description of choice:
The frequency set in this parameter will be centered
around parameters 230 Frequency bypass 1 and 231
Frequency bypass 2.
230 Frequency bypass 1 (FREQ. BYPASS 1)
231 Frequency bypass 2 (FREQ. BYPASS 2)
Value:
0 - 1000 Hz
0.0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of mechanical resonance problems
in the system.
Description of choice:
Enter the frequencies to be avoided. See also param-
eter 229 Frequency bypass, bandwidth.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
58 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2822

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2822 and is the answer not in the manual?

Danfoss VLT 2822 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2822
CategoryDC Drives
LanguageEnglish

Related product manuals