464 Wakeup Pressure
(Wakeup Pressure)
Value:
Par. 204 Ref
MIN
– par. 215 - 218 Setpoint
0
Function:
When in Sleep mode the adjustable frequency drive
will wake up when the pressure is below the Wakeup
pressure for the time set in parameter 462 Enhanced
sleep mode timer.
Description of choice:
Set an appropriate value for the system. The unit is set
in parameter 416.
465 Minimum pump frequency
(Pump min. freq.)
Value:
Value par. 201 f
MIN
– par. 202 f
MAX
(Hz)
20
Function:
This parameter is linked to parameter 467 Minimum
Power and is used for no/low-flow power curve.
Description of choice:
Enter a value equal or close to the desired minimum
frequency set in parameter 201 Output frequency low
limit, f
MIN
. Please note that the extension of the no/low-
flow power curve is limited by parameters 201 and 202,
and not by parameters 465 and 466.
466 Maximum Pump Frequency
(Pump max. freq)
Value:
Value par. 201 f
MIN
- par. 202 f
MAX
(Hz)
50
Function:
This parameter is linked to parameter 468 Maximum
pump power and is used for the no/low-flow power
curve.
Description of choice:
Enter a value equal or close to the desired maximum
frequency set in parameter 202 Output frequency high
limit, f
MAX
.
467 Minimum Pump Power
(Min. pump power)
Value:
0–500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 465 Minimum pump frequency.
Description of choice:
Enter the no/low-flow power reading at minimum pump
frequency entered in parameter 465.
Depending on pump size or curve, select W or kW in
par. 009 index [32] and [8] for fine tuning.
468 Maximum Pump Power
(Max. pump power)
Value:
0–500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 466 Minimum pump frequency.
Description of choice:
Enter the no/low-flow power reading at maximum
pump frequency entered in parameter 466.
Depending on pump size or curve, select W or kW in
par. 009 index [32] and [8] for fine tuning.
469 No Flow Power Compensation
(NF power comp)
Value:
0.01 - 2
1.2
Function:
This function is used for an off-set of the no/low-flow
power curve, which can be used as a safety factor or
for fine tuning the system.
Description of choice:
Description The factor is multiplied to the power val-
ues. E.g., 1.2 will increase the power value with 1.2
over the whole frequency range.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark 81
Programming

Table of Contents

Other manuals for Danfoss VLT 2822

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2822 and is the answer not in the manual?

Danfoss VLT 2822 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2822
CategoryDC Drives
LanguageEnglish

Related product manuals