617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615 Fault log: Fault
code .
Description of choice:
Read out as one value.
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Resetting parameter 602 kWh counter to zero.
Description of choice:
If Reset [1]is selected and you press the [OK] key, the
variable frequency drive's kWh counter is reset to zero.
This parameter cannot be selected via serial commu-
nication.
NOTE
When the [OK] key is activated, the coun-
ter is reset to zero.
619 RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Resetting of parameter 601 Hours run to zero.
Description of choice:
If Reset [1] is selected and you press the [OK] key, the
variable frequency drive's parameter 601 is reset to
zero Hours run. This parameter cannot be selected via
serial communication.
NOTE
When the [OK] key is activated the pa-
rameter is reset to zero.
620 Operation Mode
(OPERATION MODE)
Value:
Normal operation (NORMAL OPERATION) [0]
Control card test (CONTROL CARD TEST) [2]
Initialize (INITIALIZE) [3]
Function:
In addition to its normal function, this parameter can
be used to test the control card.
There is also the opportunity to perform an initialization
at the factory setting for all parameters in all Setups,
with the exception of parameters 500 Address, 501
Baudrate, 600-605 Operating data and 615-617 Fault
log.
Description of choice:
Normal function [0] is used for normal operation of the
motor.
Control card test [2] is selected if you wish to check the
control card's analog/digital inputs, analog/digital out-
puts, relay outputs and 10 V and 24 V voltages.
The test is performed as follows:
27 - 29 - 33 - 46 are connected.
50 - 53 are connected.
42 - 60 are connected.
12 - relay terminal 01 is connected.
18 - relay terminal 02 is connected.
19 - relay terminal 03 is connected.
See also the DeviceNet manual MG.90.BX.YY for fur-
ther details.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
94 MG.27.A2.22 - VLT
®