weight. It is used in particular for applications in which
a cone anchor motor is applied. The cone anchor mo-
tor can break away using parameter 130 Start frequen-
cy and parameter 131 Voltage at start.
122 Function at stop
(FUNCTION AT STOP)
Value:
Coasting (COAST) [0]
DC hold (DC HOLD) [1]
Function:
This is where to choose the function of the variable
frequency drive after the output frequency has become
lower than the value in parameter 123 The min. fre-
quency for activation of function at stop or after a stop
command and when the output frequency has been
ramped down to 0 Hz.
Description of choice:
Select Coasting [0] if the variable frequency drive is to
'let go' of the motor (inverter turned off).
Select DC hold [1] if parameter 137 DC hold voltage is
to be activated.
123
Min. frequency for activation of func-
tion at stop
(MIN.F.FUNC.STOP)
Value:
0,1 - 10 Hz
0,1 Hz
Function:
In this parameter, the output frequency is set at which
the function selected in parameter 122 Function at
stop is to be activated.
Description of choice:
Set the required output frequency.
NOTE
If parameter 123 is set higher than param-
eter 130, then the start delay function (pa-
rameter 120 and 121) will be skipped.
NOTE
If parameter 123 is set too high, and DC
hold has been chosen in parameter 122,
the output frequency will jump to the value
in parameter 123 without ramping up. This
may cause an overcurrent warning /
alarm.
126 DC brake time
(DC BRAKING TIME)
Value:
0 - 60 sec.
10 sec
Function:
In this parameter, the DC brake time is set at which
parameter 132 DC brake voltage is to be active.
Description of choice:
Set the required time.
127 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) - par. 202
Output frequency high limit, f
MAX
OFF
Function:
In this parameter, the DC brake cut-in frequency is set
at which the DC brake is to be activated in connection
with a stop command.
Description of choice:
Set the required frequency.
128 Thermal motor protection
(MOT.THERM PROTEC)
Value:
No protection (NO PROTECTION) [0]
Thermistor warning
(THERMISTOR WARN) [1]
Thermistor trip (THERMISTOR TRIP) [2]
ETR warning 1 (ETR WARNING 1) [3]
ETR trip 1 (ETR TRIP 1) [4]
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
46 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2840

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2840 and is the answer not in the manual?

Danfoss VLT 2840 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2840
CategoryDC Drives
LanguageEnglish

Related product manuals