operating situations will never exceed the
maximum permitted current in the motor.
Please note: that the current
cannot be
read out from the display.
146 Reset voltage vector
(RESET VECTOR)
Value:
*Off (OFF) [0]
Reset (RESET) [1]
Function:
When the voltage vector is reset it is set to the same
starting point each time a new process commences.
Description of choice:
Select reset (1) when running unique processes each
time they arise. This will enable repetitive precision
when stopping to be improved. Select Off (0) for ex-
ample for lifting/lowering operations or synchronous
motors. It is an advantage that the motor and the var-
iable frequency drive are always synchronized.