PNU
#
Parameter description Factory setting Range
Changes
during
operation
4-Setup
Conversion
index
Data type
700
Relay 6, function Ready signal   Yes Yes 0 5
701 Relay 6, ON delay 0 sec. 0.00-600 sec. Yes Yes -2 6
702 Relay 6, OFF delay 0 sec. 0.00-600 sec. Yes Yes -2 6
703 Relay 7, function Motor running   Yes Yes 0 5
704 Relay 7, ON delay 0 sec. 0.00-600 sec. Yes Yes -2 6
705 Relay 7, OFF delay 0 sec. 0.00-600 sec. Yes Yes -2 6
706 Relay 8, function Mains ON   Yes Yes 0 5
707 Relay 8, ON delay 0 sec. 0.00-600 sec. Yes Yes -2 6
708 Relay 8, OFF delay 0 sec. 0.00-600 sec. Yes Yes -2 6
709 Relay 9, function Fault   Yes Yes 0 5
710 Relay 9, ON delay 0 sec. 0.00-600 sec. Yes Yes -2 6
711 Relay 9, OFF delay 0 sec. 0.00-600 sec. Yes Yes -2 6
VLT
 ® 
 5000 Design Guide
MG.52.B2.02 - VLT
 ® 
 is a registered Danfoss trademark   139
Factory settings