EasyManua.ls Logo

Danfoss VLT 6102 - Page 35

Danfoss VLT 6102
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VL Serie 2800 and VL Serie 6000 Modbus RTU
Appendix A
- Examples
Message sent to Modbus RTU from Modbus master
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6+7
Slave
Address
Function Start Addr HI Start Addr LO No. of Points HI No. of Points
LO
Error Check
01 03 14 13 00 02 --
Parameter 514 (5139) = 1413
HEX
Note that the starting address of a register is the parameter number x 10 - 1 in HEX.
Message sent to Modbus master from Modbus RTU
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7+8
Slave
Address
Function Byte Count Data HI (Reg
45140)
Data LO (Reg
45141)
Preset Data
LO
Data LO (Reg
45141)
Error Check
01 03 04 00 00 01 2C --
Byte 3-byte 6: Value 0000012C
HEX
= 300 = 3 Amps
All values are in hexadecimal.
å EXAMPLE 6: Read Parameter 609 [8]
"Log: Reference"
This example shows how to read an index parameter. Holding register 9 - Array Index.
Modbus Function 06
HEX
Preset Single Register
Set Array Index to 8
Message sent to Modbus RTU from Modbus master
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6+7
Slave
Address
Function Register Addr
HI
Register Addr
LO
Preset Data HI Preset Data LO Error Check
01 06 00 08 00 08 --
Message sent to Modbus master from Modbus RTU
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6+7
Slave
Address
Function Register Addr
HI
Register Addr
LO
Preset Data HI Preset Data LO Error Check
01 06 00 08 00 08 --
Modbus Function 03
HEX
Read Holding register
Read value of parameter 609 [8]
Message sent to Modbus RTU card from Modbus master
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6+7
Slave
Address
Function Start Addr HI Start Addr LO No. of
Registers HI
No. of
Registers LO
Error Check
01 03 17 69 00 01 --
MG.10.S1.22 - VLT is a registered Danfoss trademark
35

Related product manuals