Bit 15, Safe function pending
• Bit 15 = 0, No safe function is pending.
• Bit 15 = 1, A safe function is pending.
Bit 16, General reset
• Bit 16 = 0, No change in state.
• Bit 16 = 1, A general reset is done.
Bit 17, Customization confirmed
• Bit 17 = 0, No change in state.
• Bit 17 = 1, Customization confirmed.
Bit 18, Customization aborted
• Bit 18 = 0, No change in state.
• Bit 18 = 1, Customization aborted.
Bit 19, Customization requested
• Bit 19 = 0, No change in state.
• Bit 19 = 1, Customization requested.
Bit 20, Suspension of speed monitoring
• Bit 20 = 0, No change in state.
• Bit 20 = 1, Suspension of speed monitoring - see error code.
Bit 21, Power up self test warning
• Bit 21 = 0, No change in state.
• Bit 21 = 1, A power-up self-test warning is issued.
Bit 22, Digital input 1 offline test warning
• Bit 22 = 0, No change in state.
• Bit 22 = 1, Digital input 1 offline test warning.
Bit 23, Digital input 2 offline test warning
• Bit 23 = 0, No change in state.
• Bit 23 = 1, Digital input 2 offline test warning.
Bits 24–31
These bits indicate a reason for internal or external errors. For more information, see the error codes.
Parameter 42-91 Safe Option Status 2 indicates which digital input of the safety option is activated, in pending state or in blank initial
state.
Configuring the Safety Option
Installation Guide | VLT®Safety Option MCB 152