Cable lengths and cross-sections
Max grid cable length (direct internal connection to drive) Unlimited (determined by voltage drop)
Maximum cross-section to control terminals, rigid wire 1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross-section to control terminals, flexible cable 1 mm
2
/18 AWG
Maximum cross-section to control terminals, cable with enclosed core 0.5 mm
2
/20 AWG
Minimum cross-section to control terminals 0.25 mm
2
/4 AWG
CT terminals specification
CT number 3 (one for each phase)
The AAF burden equals 2 mΩ
Secondary current rating 1 A or 5 A (hardware set-up)
Accuracy Class 0.5 or better
Digital inputs
Programmable digital inputs 2 (4)
Terminal number 18, 19, 27
*
, 29
*
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN > 19 V DC
Voltage level, logic '1' NPN < 14 V DC
Maximum voltage on input 28 V DC
Input resistance, R
i
approx. 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
*) Terminals 27 and 29 can also be programmed as output.
Control card, RS-485 serial communication
Terminal number 68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61 Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs 2
Terminal number 27, 29
1)
Voltage level at digital/frequency output 0–24 V
Max. output current (sink or source) 40 mA
1) Terminal 27 and 29 can also be programmed as input.
Control card, 24 V DC output
Terminal number 13
Max. load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Specifications
Instruction Manual
162 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
1111

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals