VLT
®
FCD Series
All about FCD
300
Safeguards:
Electronic thermal motor protection against overload.
Temperature monitoring of the power module ensures that the frequency converter cuts
out if the temperature reaches 100 °C. An overload temperature cannot be reset until the
temperature of the power module is below 70 °C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter will cut out.
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if
the intermediate circuit voltage is too low or too high.
The frequency converter is protected against earth fault on motor terminals U, V, W.
MG.04.B7.02 - VLT is a registered Danfoss trademark