on the motor speed. The FF factor provides high dy-
namism when changing the set point and less
overswing.
Description of choice:
The required % value can be selected in the interval
f
MIN
-f
MAX
. Values over 100 % are used if the set
point variations are only small.
452
452 Controller range
(PID CONTR. RANGE)
Value:
0 - 200 %
10 %
Function:
This parameter is only active if in parameter 100
Conguration the selection made is Speed regula-
tion, closed loop.
The controller range (bandwidth) limits the output
from the PID controller as a % of motor frequency
f
M,N
.
Description of choice:
The required % value can be selected for motor fre-
quency f
M,N
. If the controller range is reduced the
speed variations will be less during initial tuning.
456
456 Brake Voltage Reduce
(BRAKE VOL REDUCE)
Value:
0 - 50 V
0
Function:
The user sets the voltage by which the level for
resistor braking is reduced. It is only active when re-
sistor in parameter 400 is selected.
Description of choice:
The greater the reduction value, the faster the reac-
tion to a generator overload. Should only be used if
there are problems with overvoltage in the intermedi-
ate circuit.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.A1.02 - VLT is a registered Danfoss trade mark
93
Programming

Table of Contents

Other manuals for Danfoss VLT FCD 330

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 330 and is the answer not in the manual?

Danfoss VLT FCD 330 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 330
CategoryDC Drives
LanguageEnglish

Related product manuals