Parameter Range Default Usage
3-10 Preset Reference
-100–100% 0 Enter the set point.
3-41 Ramp 1 Ramp Up Time
0.05–3600.0 s Size related
Ramp-up time from 0 to rated 1-23 Motor
Frequency if asynchron motor is selected;
ramp up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected.
3-42 Ramp 1 Ramp Down Time
0.05–3600.0 s Size related
Ramp-down time from rated 1-23 Motor
Frequency to 0 if asynchron motor is selected;
ramp down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected.
4-12 Motor Speed Low Limit [Hz]
0–400 Hz 0.0 Hz Enter the minimum limit for low speed.
4-14 Motor Speed High Limit [Hz]
0–400 Hz 100 Hz Enter the minimum limit for high speed.
4-19 Max Output Frequency
0–400 100 Hz Enter the maximum output frequency value.
6-29 Terminal 54 mode
[0] Current
[1] Voltage
1 Select if terminal 54 is used for current or
voltage input.
6-20 Terminal 54 Low Voltage
0–10 V 0.07 V Enter the voltage that corresponds to the low
reference value.
6-21 Terminal 54 High Voltage
0–10 V 10 V Enter the voltage that corresponds to the low
high reference value.
6-22 Terminal 54 Low Current
0–20 mA 4 mA Enter the current that corresponds to the high
reference value.
6-23 Terminal 54 High Current
0–20 mA 20 mA Enter the current that corresponds to the high
reference value.
6-24 Terminal 54 Low Ref./Feedb.
Value
-4999–4999 0 Enter the feedback value that corresponds to
the voltage or current set in 6-20 Terminal 54
Low Voltage/6-22 Terminal 54 Low Current.
6-25 Terminal 54 High Ref./Feedb.
Value
-4999–4999 50 Enter the feedback value that corresponds to
the voltage or current set in 6-21 Terminal 54
High Voltage/6-23 Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
0–10 s 0.01 Enter the filter time constant.
20-81 PI Normal/ Inverse Control
[0] Normal
[1] Inverse
0
Select [0] Normal to set the process control to
increase the output speed when the process
error is positive. Select [1] Inverse to reduce
the output speed.
20-83 PI Start Speed [Hz]
0–200 Hz 0 Hz Enter the motor speed to be attained as a
start signal for commencement of PI control.
20-93 PI Proportional Gain
0–10 0.01 Enter the process controller proportional gain.
Quick control is obtained at high amplifi-
cation. However, if the amplification is too
great, the process may become unstable.
20-94 PI Integral Time
0.1–999.0 s 999.0 s Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
30-22 Locked Rotor Detection
[0] Off
[1] On
[0] Off
30-23 Locked Rotor Detection Time [s]
0.05–1 s 0.10 s
Table 4.5 Set-up Wizard for Closed-loop Applications
Programming
Quick Guide
MG18A622 Danfoss A/S © 08/2014 All rights reserved. 37
4 4

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers: