Fault
number
Alarm/
warning bit
number
Fault text Warning Alarm Trip
locked
Cause of problem
57 AMA timeout X
Try to start the AMA again a number of times, until the AMA
is carried out.
NOTICE!
Repeated runs may heat the motor to a level where
the resistance Rs and Rr are increased. In most cases,
however, this is not critical.
58 AMA internal X X Contact the local Danfoss supplier.
59 25 Current limit X
The current is higher than the value in 4-18 Current Limit.
60 44 External Interlock X
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
external interlock and reset the adjustable frequency drive
(via serial communication, digital I/O, or by pressing reset
button on keypad).
66 26
Heatsink
Temperature Low
X
This warning is based on the temperature sensor in the IGBT
module (on 400 V, 30–90 kW (40–125 HP) and 600 V units).
69 1 Pwr. Card Temp X X X
The temperature sensor on the power card exceeds the
upper or lower limits.
70 36
Illegal FC configu-
ration
X X
The control card and power card are not matched.
79
Illegal power
section configu-
ration
X X
Internal fault. Contact the local Danfoss supplier.
80 29 Drive initialized X All parameter settings are initialized to default settings.
87 47 Auto DC Braking X The drive is auto DC braking.
95 40 Broken Belt X X
Torque is below the torque level set for no load, indicating a
broken belt. See parameter group 22-6* Broken Belt Detection.
126 Motor Rotating X High back emf voltage. Stop the rotor of the PM motor.
200 Fire Mode X Fire mode has been activated.
202
Fire Mode Limits
Exceeded
X
Fire mode has suppressed one or more warranty voiding
alarms.
250 New spare part X X
The power or switch mode power supply has been
exchanged (on 400 V, 30–90 kW (40–125 HP) and 600 V
units). Contact the local Danfoss supplier.
251 New Typecode X X
The adjustable frequency drive has a new type code (on 400
V, 30–90 kW (40–125 HP) and 600 V units). Contact the local
Danfoss supplier.
Table 5.1 Warnings and Alarms
Warnings and Alarms Quick Guide
MG18A622 Danfoss A/S © 08/2014 All rights reserved. 45
5 5

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals