EasyManua.ls Logo

Danfoss VLT HVAC Basic Drive FC 101

Danfoss VLT HVAC Basic Drive FC 101
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RFI filter
type
Conduct emission. Maximum shielded cable length (ft [m]) Radiated emission
Industrial environment
EN 55011
Class A Group 2
Industrial environment
Class A Group 1
Industrial environment
Class B
Housing, trades and
light industries
Class A Group 1
Industrial environment
Class B
Housing, trades and
light industries
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
H4 RFI filter (EN55011 A1, EN/IEC61800-3 C2)
0.25–11 kW
3x200–240 V
IP20
25 50 20 Yes Yes No
0.37–22 kW
3x380–480 V
IP20
25 50 20 Yes Yes No
H2 RFI filter (EN 55011 A2, EN/IEC 61800-3 C3)
15–45 kW
3x200–240 V
IP20
25 No No
30–90 kW
3x380–480 V
IP20
25 No No
0.75–18.5
kW
3x380–480 V
IP54
25 Yes
22–90 kW
3x380–480 V
IP54
25 No No
H3 RFI filter (EN55011 A1/B, EN/IEC 61800-3 C2/C1)
15–45 kW
3x200–240 V
IP20
50 20 Yes No
30–90 kW
3x380–480 V
IP20
50 20 Yes No
0.75–18.5
kW
3x380–480 V
IP54
25 10 Yes
22–90 kW
3x380–480 V
IP54
25 10 Yes No
Table 6.7 EMC Emission Test Results